Rectiverter 48V 230/1500 48/1200 & 115/750 48/600
Doc 241123.100.DS3v3

Rectifier & Inverter in one box

Built on HE technology from the Flatpack2 HE rectifier family the Rectiverter 230/1500 48/1200 provides backed up power for 230 VAC loads with minimum losses and footprint.

It is a 3 port device capable of charging the 48V battery and simultaneously provides power for the AC and DC loads.
During mains outage the Rectiverter feeds AC loads using energy stored in the battery.

APPLICATIONS

TELECOM
LTE/4G/WiMAX
Distributed antenna system
Broadband
POWER UTILITIES
Switch tripping and SCADA
Låg & High voltage switchgear
Transformer & SUB stations
Power Generation & Distribution
Control & protection
SCADA system
RAILWAY & METRO INFRASTRUCTURE
Signaling and communications
Control centers
MARINE
Communication onboard ships
OTHER
Rural electrification

Specifikationer

Models / ordering information 230/1500 230/1500 230/1500 115/750 115/750 115/750
48/1200 48/150 48/0 48/600 48/75 48/0
Part number 241123.100 241123.101 241123.102 241123.100L 241123.101L 241123.102L
AC OUTPUT DATA
Spänning (default) / (adjustable range) 230 VAC / 200 – 240 VAC 115 VAC / 100 – 127 VAC
Frequency (default inverter mode) 50 Hz (adaptive) 60 Hz (adaptive)
Frequency (set-able inverter mode) 50Hz, 60Hz or last synced 50/60Hz (adaptive), 94-106Hz
Power maximum (continuous / overload (<15s)) 1200 W (1500 VA) / 2000 VA 600 W (750 VA) / 1000 VA
Load sharing ±5% of active power from 10 till 100% load
Current maximum (continuous / overload (<15s)) 6.5 ARMS / 8.7 ARMS
Current (maximum) Quick trip (20ms) 32 A (6 x nominal)
Hold up (Voltage dips) (before switching to battery) 5 ms 5 ms
THD < 1.5 % at resistive load
Protection Fuse in L, Hot pluggable, Varistor
DC OUTPUT DATA
Spänning (default) / (adjustable range) 53.5 VDC / 43 – 58 VDC
Driva (maximum @nominal input) 1200 W 1) 150 W 0 W 600 W 1) 75 W 0 W
Current (maximum @VOUT ≤ 48 VDC) 25 A 1) 3.13 A – 12.5 A 1) 1.56 A –
Current sharing (10 – 100% load) ±5% of maximum current from 10 till 100% load
Static Voltage regulation (10 – 100% load) ±0.5%
Dynamic Voltage regulation ±5.0% for 10-90% eller 90-10% load variation, regulation time < 50ms
Ripple < 200 mVPP , 30 MHz bandwidth
Protection Short circuit proof, Over voltage shutdown, Reversed polarity, Reversed polarity and Fuse
INPUT DATA
AC Mains Input Voltage (range / LV disconnect) 185 – 275 VAC / 170 VAC 95 – 140 VAC / 85 VAC
AC Current (maximum) 11.5 ARMS 9.1 ARMS 2) 8.2 ARMS 2) 11.3 ARMS 10.1 ARMS 2) 9.2 ARMS 2)
Frequency (default: sync range) 47-53 & 57-63 Hz 47-53 & 57-63 Hz
Frequency (set-able: sync range) 47-53 Hz, 57-63 Hz or both (adaptive)
Power Factor / THD > 0.985 at 50% load or more / < 3.5%
AC Input Protection Fuse in L and N, Hot pluggable, Varistor
DC Voltage nominal / extended range3) 45 – 58 VDC / 40 – 45 VDC
DC Current (maximum) 32 A / 45A during overload (15s) 16 A / 22.5A during overload (15s)
OTHER SPECIFICATION
Effektivitet >96% (mains mode), >94% (inverter mode) >92% (mains mode), >91% (inverter mode)
Isolation 3.6 kVDCACPorts to PE, 3 kVACACPorts to DCPort/CAN, 710 VDC – DCPort to PE, 60 VDC – DCPort to CAN
Alarms: Red LED Low and high mains input voltage shutdown, High and low temperature shutdown, Rectiverter Failure, Alarm relay [NO max 75 VDC / 100 mA] Overvoltage shutdown on output, Fan failure, Low output voltage alarm, CAN bus failure, Sync bus (AC output OR DC output alarms) lost and Sync fail
Warnings: Yellow LED Rectiverter in power de-rate mode or in power or current limit mode on DC or AC port, Remote output current limit activated, Loss of CAN communication with controller
Normal operation: Green LED AC output and/or DC output on and ok
MTBF (Telcordia SR-332 Iss.I method III (a)) 260 000 timmar (@ Tambient : 25 °C)
Driftstemperatur -40 to +75°C (-40 to +167°F), humidity 5 – 95% RH non-condensing
Temperature de-rating above 55°C (131°F) 1200W to 480W @ 75°C (167°F) for each, AC and DC, outputs (total power 2000W to 800W)
Förvaringstemperatur -40 to +85°C (-40 to +185°F), humidity 0 – 99% RH non-condensing
Dimensions[WxHxD] / Vikt 109 x 41.5 x 327mm (4.25 x 1.69 x 13″) / 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC/EN 62040-1:2008+A1:2013 UL 60950-1:2014, UL1778:2014, C22.2 No. 107.3-14
EMC EN 61000-6-1:2007 / -2:2005 / -3:2007+A1:2010 / -4:2007+A1:2010, EN 62040-2:2006 EN50121-4:2015/-5:2015, ETSI EN 300 386 V.1.6.1, FCC CFR 47 Del 15
2011/65/EU (RoHS) & 2012/19/EU (WEEE) / ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)
Environment Normal operating conditions as per IEC/EN 62040-3:2011 clause 4.2. Other operating conditions as per IEC 62040-3:2011 clause 4.3, must be advised
1) AC load has priority. Maximum available DC output power and current is dependent on 2) If DC port is overloaded pulling the voltage below 43V the input current may increase above this level.
instant AC load och AC input spänning; dvs maximum 800W/16.6A at full AC power och nominal 3) Reduced performanceno over load support, and for 200 – 240 VAC output THD will increased and maximum input for 230VAC. output power de-rates (to 970W for 230 VAC @ 40 VDC)

______________________________________________________

Wuhan Unique Mechanical And Electrical Equipment Co., LTD. is a high-tech enterprises with a combination of of science, industry and trade. We mainly engaged in R&D and manufacturing of network center room equipment, such as PDU, ODF, CMA, Fiber Spool Frame, Network Panel, Network Cabinet, OF Jointing Box, Fiber Optic Connector, ADSS Cable, Micro Fiber, Pigtail, Patch Cord, UTP Cable, etc. Provide high level of technical consultation and technical services.