7.2kv 12kv Medium Voltage Vacuum Switch for Switchgear (VCKG3)

Modelo NÃO.
VCKG3

Mechanical Life Time
1000000 Times

Mechanical Lock Operation Frequency
120 Times/H

Tri-Phase Asynchronous Time
Máx.:2ms

Over Travel
1.6-2milímetros

Pacote de transporte
Caixa

Marca comercial
VACEM

Origem
Wenzhou, China

Código HS
8535900090

Descrição

1.General description

VACG series AC M.V. vacuum contactor is suitable for power system of AC 50Hz,main circuit rated voltage up to 12kv,rated current up to 630A,
for remote making and breaking,frequently starting and controlling AC motors,more suitable for matching with fuse and a variety of protection device to replace vacuum circuit breaker.
The contactor complies GB/T 14808,IEC 60470 and JB/T 7122 standard,the main performance indicators have reached the international level.

2. Normal using conditions

um. Environment temperature : -5ºC~+40ºC, and average value is no more than +35ºC within 24 hour.
b. Altitude: no more than 1000m.
c. Atmospheric conditions: monthly highest humidity in the most wet month is no more than 90% and monthly average minimum temperature
shall be 25ºC. Condensation on the products due to temperature changes shall be considered.
d. Impact vibration: The place is without extensive shaking, impact, and vibration.
e. The place is without explosion hazard, enchant gas and sleet.
f. No rain and snow in places
g. Pollution degree: Three grade
h. Installation type: .III
eu. Installation condition: Slant angle between installation surface and vertical surface is no more than 15°.

3.Main technical parameter

Tipo Unidade VACG-160~630/7.2 VACG-160~630/12
Rated voltage kV 7.2 12
Rated current UMA 160 250 400 630 160 250 400 630
Making capacity A/100times 1600 2500 4000 6300 1600 2500 4000 6300
Breaking capacity A/25times 1280 2000 3200 5000 1280 2000 3200 5000
Rated P.F. withstand voltage kV 28 42
Mechanical life time times 100,0000
Rated operating frequency times/h 300
Short-time operating frequency(20é) times/h 1000
Mechanical lock operation frequency times/h 120
Clearance between open contacts milímetros 4±0.2 6±0.5
Over travel milímetros 1.8±0.2 1.8±0.2
Closing time ms ≤80
Opening time ms ≤40
Main circuit resistance μΩ ≤200
Tri-phase asynchronous time ms ≤2

For Vacuum Circuit Breaker, pls click: https://china-vacem.en.made-in-china.com/product-group/roqEnxmCTUYh/Vacuum-Circuit-Breaker-catalog-1.html

4.International fairs


5. Company show7.2kv 12kv Medium Voltage Vacuum Switch for Switchgear (VCKG3)
7.2kv 12kv Medium Voltage Vacuum Switch for Switchgear (VCKG3)7.2kv 12kv Medium Voltage Vacuum Switch for Switchgear (VCKG3)7.2kv 12kv Medium Voltage Vacuum Switch for Switchgear (VCKG3)7.2kv 12kv Medium Voltage Vacuum Switch for Switchgear (VCKG3)