Description
Project | Unit | R134a Units | R22 Units | |
Environmental side | Dry bulb temperature | ºC | -35-21ºC | -35-21ºC |
Use side | Water outlet temperature | ºC | 35-70ºC | 35-55ºC |
Water flow | m3/h | Rated Flow±15% | Rated Flow±15% | |
Allowable voltage range | V | Rated voltage±5% | Rated voltage±5% | |
Three-phase voltage imbalance rate | / | ±2% | ±2% | |
Allowable frequency range | HZ | Rated frequency±2% | Rated frequency±2% | |
Note if water outlet temperature is higher than 70ºC |
Model | KMAD-100 | KMAT-150 | KMAT-200 | KMAT-240 | KMAT-280 | KMAT-330 | |
The refrigerant | R134a | ||||||
Heating | KW | 100 | 150 | 200 | 240 | 280 | 330 |
Input power (rated condition) |
KW | 38 | 55 | 70 | 85 | 100 | 113 |
power supply | 3φ-380V-50HZ | ||||||
protective device | Reverse phase loss protection, over current protection, motor temperature protection, high and low voltage protection, high and low temperature protection, water flow protection |
||||||
Refrigeration circuit | 1 | ||||||
Energy control (%) | 0,50,75,100 | ||||||
Refrigerant charge (kg) | 100 | 150 | 160 | 180 | 200 | 220 | |
Finned heat exchanger | Copper tube wearing hydrophilic corrugated aluminum sheet | ||||||
Fan | Form | Axial Flow | |||||
Flow (m3/h) | 60000 | 60000 | 90000 | 90000 | 120000 | 120000 | |
Power (kw) | 6 | 6 | 9 | 9 | 12 | 12 | |
Water side maximum pressure MPa | Form | Shell and tube heat exchanger | |||||
Water side maximum pressure MPa | 1 | ||||||
Import and export pipe diameter | DN65 | DN80 | DN100 | DN100 | DN125 | DN125 | |
Hot water flow | 17.2 | 25.8 | 34.4 | 41.3 | 49 | 56.8 | |
Water pressure drop | 38 | 42 | 45 | 48 | 52 | 55 | |
Running noisedB(A) | 75 | 77 | 78 | 80 | 81 | 82 | |
Unit length(mm) | 3360 | 3360 | 5000 | 5000 | 6000 | 6000 | |
Unit width(mm) | 2260 | 2260 | 2230 | 2230 | 2230 | 2230 | |
Unit height(mm) | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | |
Unit weight(kg) | 4000 | 4300 | 6400 | 6700 | 8100 | 8500 | |
Running weight(kg) | 4500 | 4800 | 7000 | 7300 | 8700 | 9200 | |
1. According to GB/T 25127.1-2010, the nominal heating standard: ambient dry bulb temperature -12°C, ambient wet bulb temperature -14°C, hot water outlet temperature 41°C, water flow 0.172 m3 / h * kW; 2, The ambient temperature range: -25 ° C ~ 21 ° C; Tot water temperature range: 35°C ~ 70°C; 3. The unit parameters are subject to change without prior notice. The specific parameters are subject to the product nameplate; 4. KMAD-100 unit is a heating and cooling unit, GB/T 25127.1-2010 national standard nominal cooling capacity is 5. ★ for the upcoming product model. |
|||||||
Model | KMAT-130A* | KMAT-190A* | KMAT-290A* | KMAT-350A | KMAT-350AV | |
The refrigerant | R22 | |||||
Heating | KW | 130 | 190 | 290 | 350 | 350 |
Input power (rated condition) |
KW | 45 | 65 | 98 | 118 | 120 |
power supply | 3φ-380V-50HZ | |||||
protective device | Reverse phase loss protection, over current protection, motor temperature protection, high and low voltage protection, high and low temperature protection, water flow protection |
|||||
Refrigeration circuit | 1 | |||||
Energy control (%) | 0,50,75,100 | |||||
Refrigerant charge (kg) | 160 | 180 | 200 | 220 | 220 | |
Finned heat exchanger | Copper tube wearing hydrophilic corrugated aluminum sheet | |||||
Fan | Form | Axial Flow | ||||
Flow (m3/h) | 60000 | 90000 | 120000 | 120000 | 120000 | |
Power (kw) | 6 | 9 | 12 | 12 | 12 | |
Water side maximum pressure MPa | Form | Shell and tube heat exchanger | ||||
Water side maximum pressure MPa | 1 | |||||
Import and export pipe diameter | DN80 | DN100 | DN125 | DN125 | DN125 | |
Hot water flow | 22.4 | 32.7 | 49 | 60.2 | 60.2 | |
Water pressure drop | 45 | 48 | 52 | 55 | 55 | |
Running noisedB(A) | 80 | 80 | 82 | 85 | 85 | |
Unit length(mm) | 3500 | 5000 | 6000 | 6000 | 6000 | |
Unit width(mm) | 2230 | 2230 | 2230 | 2230 | 2230 | |
Unit height(mm) | 2500 | 2500 | 2500 | 2500 | 2500 | |
Unit weight(kg) | 4500 | 6200 | 8000 | 8500 | 8500 | |
Running weight(kg) | 5000 | 6700 | 8700 | 9000 | 9000 | |
1. According to GB/T 25127.1-2010, the nominal heating standard: ambient dry bulb temperature -12°C, ambient wet bulb temperature -14°C, hot water outlet temperature 41°C, water flow 0.172 m3/h*kW; 2. The ambient temperature range: -35°C ~21°C; Tot water temperature range: 35°C ~55°C; 3. The unit parameters are subject to change without prior notice. The specific parameters are subject to the product nameplate. 4. ★ for the upcoming product model. |
||||||
FAQ
Q1: Are you factory or trade company?
A1: We are factory.
Q2: What the exactly address of your factory?
A2: No. 366, YangzhuangBang Street, Pingxing Rd., Xindai Town, Pinghu, Zhejiang Province, China
Q3: Warranty terms of your machine?
A3: Two years warranty for the machine and technical support according to your needs.
Q4: Will you provide some spare parts of the machines?
A4: Yes, of course.
Q5: How long will you take to arrange production?
A5: 380V 50HZ we can delivery the goods within 10 days. Other electricity or other color we will delivery within 22 days
Q6: Can you accept OEM orders?
A6: Yes, with professional design team, OEM orders are highly welcome.
DENAIR Factory
DENAIR Exhibition
DENAIR Customer Case:
DENAIR Packing & Shipping