48VDC/110DC/220VDC Thyristor Rectifier DC Battery Charger with Ni-CD Battery Bank

Model NO.
GZDT

Size
A

Certification
CE

Socket Type
Southamerica

Recyclable
Non-Recyclable

Transport Package
Wooden

Specification
30VDC/48VDC/110VDC/220VDC

Trademark
HEMG

Origin
China

Production Capacity
5000set/Year

Description

7.10 Technical Particulars & Guarantees of
110V DC Sub-Station Battery
 

SL. No. Description Unit BPDB’s Requirement Manufacturers Guaranteed Particulars
1 Manufacturers name & country  To be mentioned HEMG/CHINA
2 Manufacturers model no. To be mentioned GNZ100
3 Type Nickel Cadmium Alkaline (enclosed type) Nickel cadmium Alkaline(open type)
4 Operating Voltage V DC 110 110
5 Continuous Discharge Current at rate of 10 hour & Final Cell Voltage 1.1 Volt Amp 10 10A
6 Short Time Discharge Current at rate of 2 hour & Final Cell Voltage 1.1 Volt Amp 50 50A
7 Electrolyte type To be mentioned Alkaline solutions
8 Capacity at 10 hour rate AH 100 100Ah
9 Discharge Voltage Volt 1.3 Per Cell 1.3 Per Cell
10 Charging Voltage (Normal)  Volt 1.6 Per Cell 1.6 Per Cell
11 Number of cells Nos. 92 nos. +5nos. Spare 92 nos.+5 nos. Spare
12 Voltage per cell V 1.2 1.2V
13 Charging Voltage (Maximum) Volt 1.75 Per Cell 1.75 Per cell
14 Normal float charge rate A To be mentioned 0.2A-0.3A
15 Maximum boost charge rate A To be mentioned 30A
16 Amp hour efficiency at:
a)     10 hour rate
b)     1 hour rate
 
%
%
 
To be mentioned
To be mentioned
108%
60%
17 Size of cell Mm To be mentioned 165*105*345mm(ABS or PP container)
18 Weight of cell and electrolyte Kg To be mentioned 9.3Kg/1.70Kg
19 Standard As per Latest Edition of applicable IEC-60623 IEC-60623
20 Specific gravity of electrolyte   To be mentioned 1.20±0.02g/cm3
21 Release pressure for valve regulated type Kg/m2 To be mentioned 0.005×10-4Kg/m2
22 Volume of electrolyte per cell Ml To be mentioned 1.8L
23 Volume of reserve electrolyte per cell Ml To be mentioned 0.78L
24 No of electrode plates per cell Nos. To be mentioned Positive 12 pcs
Negative 11 pcs
25 Type of racks
a)     Height
b)     Width
c)     Depth
   
 
To be mentioned
Steel
3360
640
626
26 Cell dimension:
a)     Height
b)     Width
c)     Depth
   
To be mentioned
 
165
105
345
27 Rack Dimensions
a)     Height
b)     Width
c)     Depth
     
3360
640
626
28 Recycling facilities for unserviceable batteries available or not Y/N To be mentioned No

 
Seal & Signature of the Manufacturer                                Seal & Signature of the Bidder

7.11 Technical Particulars & Guarantees of Sub-Station
110V DC Battery Charger
 

SL. No. Description Unit BPDB’s Requirement Manufacturers Guaranteed Particulars
1 Manufacturers name & country  To be mentioned HEMG
2 Manufacturers model no. To be mentioned GZDT-110V/50A
3 Rating To be mentioned 10KVA
4 Rated Input voltage range V AC 415 V ± 10% 415V±10%
5 Rated Frequency Hz 50 Hz (±3%) 50Hz±3%
6 No of Phase 03 03
7 Control   Shall be mentioned PLC+Touch screen
8 Communication module for station automation   Shall be provided 485
9 Rectifier type   Silicon Silicon
10 Nominal output voltage V DC 110 110V
11 Charging operating control   Boost and floating charge, automatic with manual operation manual operation
12 Output current A DC ≥ 40 50A
13 Continuous current rating   110% of rated current 110% of rated current
14 Efficiency % ≥ 85 ≥85%
15 Voltage regulation % ± 0.5 ≤±0.5%
16 Ripple voltage mV ≤ 150 ≤150
17 Boost charging voltage V/cell 1.6 to 1.75 (programmable) programmble
18 Boost charging time Hour Programmable programmable
19 Operating temperature °C 0 to 50 0~50
20 Humidity % 95 95%
21 Audible noise dB ≤ 65 ≤65
22 Facilities for paralleling with another charger   Shall be provided One charger
23 Protection against surge voltage   Shall be provided Surge arrester
24 Protection against reverse polarity     Isolation diodes
25 Provision for current limiting     110%
26 Provision of constant voltage charge 90V -130V     80-160V
27 Provision of showing earth leakage current by analog meter     20mA
28 Battery Temperature compensation   Shall be incorporated. -2~3mv/ºC(20ºC)
29 Alarm annunciator independent of the microprocessor   Shall be provided PLC
30 Analog meters for voltage and current measurement of input output and battery power     
Shall be mentioned
Dc voltmeter
Dc current meter
31 Dimension   Shall be mentioned 800×600×2260mm
32 Output voltage range
a)     Normal charge
b)     Float charge
c)     Boost charge
 
V DC
V DC
V DC
 
110 V ± 1%
120 V ± 1%
150 V ± 1%
 
110 V ± 1%
120 V ± 1%
150 V ± 1%
33 Normal/boost charge independent units? Yes/No To be mentioned No
34 Output current A 50 50
35 Rated Battery Current A 20 20
36 Efficiency % To be mentioned 80%
37 Ripple Voltage % 3% 3%
38 Type of AVR Static 20V
39 Installation Break Down Voltage KV 2KV for 1 Minute 2KV for 1 Minute
40 Type of rectifier Thyristor To be mentioned Thyristor
41 MCCB      
  a)     Quantity Nos. MCB will be provided near AC input & DC Output Meet customer needs
  b)     Rating A AC input MCB-50A DC Output MCB-63A AC input MCB-50A DC Output MCB-63A
42 Standard As per Latest Edition of Applicable IEC-60146 IEC-60146