Description
Doc 241123.100.DS3 – v3
Rectifier & Inverter in one box
Built on HE technology from the Flatpack2 HE rectifier family the Rectiverter 230/1500 48/1200 provides backed up power for 230 VAC loads with minimum losses and footprint.
It is a 3 port device capable of charging the 48V battery and simultaneously provides power for the AC and DC loads.
During mains outage the Rectiverter feeds AC loads using energy stored in the battery.
APPLICATIONS
TELECOM
LTE/4G/WiMAX
Distributed antenna system
Broadband
POWER UTILITIES
Switch tripping and SCADA
Low & High voltage switchgear
Transformer & SUB stations
Power Generation & Distribution
Control & protection
SCADA system
RAILWAY & METRO INFRASTRUCTURE
Signaling and communications
Control centers
MARINE
Communication onboard ships
OTHER
Rural electrification
Specifications
Models / ordering information 230/1500 230/1500 230/1500 115/750 115/750 115/750 48/1200 48/150 48/0 48/600 48/75 48/0 |
Part number 241123.100 241123.101 241123.102 241123.100L 241123.101L 241123.102L |
AC OUTPUT DATA |
Voltage (default) / (adjustable range) 230 VAC / 200 – 240 VAC 115 VAC / 100 – 127 VAC |
Frequency (default inverter mode) 50 Hz (adaptive) 60 Hz (adaptive) |
Frequency (set-able inverter mode) 50Hz, 60Hz or last synced 50/60Hz (adaptive), 94-106Hz |
Power maximum (continuous / overload (<15s)) 1200 W (1500 VA) / 2000 VA 600 W (750 VA) / 1000 VA |
Load sharing ±5% of active power from 10 to 100% load |
Current maximum (continuous / overload (<15s)) 6.5 ARMS / 8.7 ARMS |
Current (maximum) Quick trip (20ms) 32 A (6 x nominal) |
Hold up (Voltage dips) (before switching to battery) 5 ms 5 ms |
THD < 1.5 % at resistive load |
Protection Fuse in L, Hot pluggable, Varistor |
DC OUTPUT DATA |
Voltage (default) / (adjustable range) 53.5 VDC / 43 – 58 VDC |
Power (maximum @nominal input) 1200 W 1) 150 W 0 W 600 W 1) 75 W 0 W |
Current (maximum @VOUT ≤ 48 VDC) 25 A 1) 3.13 A – 12.5 A 1) 1.56 A – |
Current sharing (10 – 100% load) ±5% of maximum current from 10 to 100% load |
Static Voltage regulation (10 – 100% load) ±0.5% |
Dynamic Voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
Ripple < 200 mVPP , 30 MHz bandwidth |
Protection Short circuit proof, Over voltage shutdown, Reversed polarity, Reversed polarity and Fuse |
INPUT DATA |
AC Mains Input Voltage (range / LV disconnect) 185 – 275 VAC / 170 VAC 95 – 140 VAC / 85 VAC |
AC Current (maximum) 11.5 ARMS 9.1 ARMS 2) 8.2 ARMS 2) 11.3 ARMS 10.1 ARMS 2) 9.2 ARMS 2) |
Frequency (default: sync range) 47-53 & 57-63 Hz 47-53 & 57-63 Hz |
Frequency (set-able: sync range) 47-53 Hz, 57-63 Hz or both (adaptive) |
Power Factor / THD > 0.985 at 50% load or more / < 3.5% |
AC Input Protection Fuse in L and N, Hot pluggable, Varistor |
DC Voltage nominal / extended range3) 45 – 58 VDC / 40 – 45 VDC |
DC Current (maximum) 32 A / 45A during overload (15s) 16 A / 22.5A during overload (15s) |
OTHER SPECIFICATION |
Efficiency >96% (mains mode), >94% (inverter mode) >92% (mains mode), >91% (inverter mode) |
Isolation 3.6 kVDC – ACPorts to PE, 3 kVAC – ACPorts to DCPort/CAN, 710 VDC – DCPort to PE, 60 VDC – DCPort to CAN |
Alarms: Red LED Low and high mains input voltage shutdown, High and low temperature shutdown, Rectiverter Failure, Alarm relay [NO max 75 VDC / 100 mA] Overvoltage shutdown on output, Fan failure, Low output voltage alarm, CAN bus failure, Sync bus (AC output OR DC output alarms) lost and Sync fail |
Warnings: Yellow LED Rectiverter in power de-rate mode or in power or current limit mode on DC or AC port, Remote output current limit activated, Loss of CAN communication with controller |
Normal operation: Green LED AC output and/or DC output on and ok |
MTBF (Telcordia SR-332 Iss.I method III (a)) 260 000 hours (@ Tambient : 25 °C) |
Operating temperature -40 to +75°C (-40 to +167°F), humidity 5 – 95% RH non-condensing |
Temperature de-rating above 55°C (131°F) 1200W to 480W @ 75°C (167°F) for each, AC and DC, outputs (total power 2000W to 800W) |
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 – 99% RH non-condensing |
Dimensions[WxHxD] / Weight 109 x 41.5 x 327mm (4.25 x 1.69 x 13″) / 1.95 kg (4.3 lbs) |
DESIGN STANDARDS |
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC/EN 62040-1:2008+A1:2013 UL 60950-1:2014, UL1778:2014, C22.2 No. 107.3-14 |
EMC EN 61000-6-1:2007 / -2:2005 / -3:2007+A1:2010 / -4:2007+A1:2010, EN 62040-2:2006 EN50121-4:2015/-5:2015, ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15 |
2011/65/EU (RoHS) & 2012/19/EU (WEEE) / ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) Environment Normal operating conditions as per IEC/EN 62040-3:2011 clause 4.2. Other operating conditions as per IEC 62040-3:2011 clause 4.3, must be advised |
1) AC load has priority. Maximum available DC output power and current is dependent on 2) If DC port is overloaded pulling the voltage below 43V the input current may increase above this level. instant AC load and AC input voltage; i.e maximum 800W/16.6A at full AC power and nominal 3) Reduced performance – no over load support, and for 200 – 240 VAC output THD will increased and maximum input for 230VAC. output power de-rates (to 970W for 230 VAC @ 40 VDC) |
______________________________________________________
Wuhan Unique Mechanical And Electrical Equipment Co., LTD. is a high-tech enterprises with a combination of of science, industry and trade. We mainly engaged in R&D and manufacturing of network center room equipment, such as PDU, ODF, CMA, Fiber Spool Frame, Network Panel, Network Cabinet, OF Jointing Box, Fiber Optic Connector, ADSS Cable, Micro Fiber, Pigtail, Patch Cord, UTP Cable, etc. Provide high level of technical consultation and technical services.