R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

Modèle NON.
AWXX

Source d'alimentation
Électrique

Type de puissance
CA

Condition
Nouvelle

Réfrigérant
R410A/R407c/R134A/R22

Échangeur de chaleur
Plate/Tube in Tube

Compressor Brand
Copeland/Panasonic/Daikin

Compressor Type
Scroll

Electric Parts
World Famous Brand

Refrigerant Valves
Emerson

Energy Recovery
Optional

Running Condition
T1 Condition or T3 High Ambient Temperature

Colour
Blanc(Standard) or Others

Used for
Commercial Building or Industrial Factory

Forfait transport
Fumigation-Free Wood Packaging

Marque déposée
AMRTA or OEM

Origine
Chine

Code SH
8418612090

Capacité de production
6000Pièces/an

La description

R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

Cooling Capacity 8 kW ~ 50 kW

Our Products Range

R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

Characteristics

Structure
Panels and base frame are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents

compresseur
Hermetic scroll type compressor, equipped with the crankcase heater and thermal protection with thermal overload cut-out and crankcase heater mounted on rubber vibration isolators

Axial fan
External rotor type axial fans, equipped with single phase direct drive motors, low noise 6 poles, protection level IP54, provided with a protective outlet grille

Évaporateur
High efficiency and low pressure drop stainless steel (AISI 316) water exchangers, with anti-freeze heating element (option) and differential pressure switch, factory insulated with flexible close cell material

Condenser
Coils are consisting of seamless copper tubes mechanically expanded into blue hydrophilic aluminum fins,100% fully quality tested; sub cooling circuit to prevent freezing at the base (facultatif); protected with metal grill

Desuperheater
High efficiency stainless steel brazed plate heat exchanger, factory insulated with flexible close cell material(facultatif)

Refrigerant circuit

Copper tube connection with charge valve, filter, sight glass, gas-liquid separator, thermostatic expansion valve, low pressure switch with automatic reset, high pressure switch with manual reset . The heat pump unit is completed also with 4-way valve, liquid receiver and one way valve

Water circuit

Built with air vent valve, water drain connection, and female-threaded hydraulic connectors

Water pump (8kW-30kW), differential pressure switch

Expansion tank (8kW-30kW)

Electric panel

Consists of:

Compressor contactor

Compressor protection breaker

Fan motor protection breaker

Control circuit protection breaker

Phase sequence relay (only for 3-phase)

Programmable microprocessor controller

Optional

Additional electric heater embedded in the coils for defrosting in low temperature ambient. It must be factory installed

Stainless steel covering

Remote condenser

Tube in tube heat exchanger

Water circuit electric heater

données techniques

Modèle Unit 20 25 30 35 40 50
Cooling *
Capacité de refroidissement kW 21.5 24.8 30 35.6 41 50.6
Cooling input (without water pump) kW 8.2 9.03 9.39 13.2 15.02 18.8
EER / 2.62 2.75 3.19 2.7 2.73 2.69
Chauffage **
Capacité de chauffage kW 26.3 29 34 41.8 47.2 60
Heating input (without water pump) kW 8.7 9.23 9.43 14.3 15.57 20.45
FLIC / 3.02 3.14 3.61 2.92 3.03 2.93
Hermetic compressor
Taper /
Quantity/ circuit / 2/2 2/2 2/2 2/2 2/2 2/2
Évaporateur
Taper /
Water flow m3/h 3.7 4.3 5.2 6.1 7.1 8.7
Water side pressure drop kPa 38 39 42 50 52 52
Water connection size millimètre DN40 DN40 DN40 DN40 DN40 DN40
Circulating pump
Entrée de puissance kW 0.75 0.75 0.92 ——— ——— ———–
Axial fans
Quantité Nr. 1 1 1 2 2 2
Airflow m3/h 9000 9000 12580 17000 17000 22000
Overal dimension
Length millimètre 1600 1600 1600 2000 2000 2000
Width millimètre 900 900 900 900 900 900
Hauteur millimètre 1080 1080 1080 1080 1080 1080
Noise level *** dB(UN) 66 66 68 70 70 70
Net weight kg 270 290 310 360 380 465

* Ambient temperature 35ºC; user side water in/out 12/7ºC.
** Ambient temperature 7ºC; user side water in/out 40/45ºC.
*** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in an ideal field (fan side).

Production Process

R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

World Famous Spare Parts

R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

Product Pictures
R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump
R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

Our Factory and Certificates

R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

Some Simple Overseas Projects

R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump

Nous contacter

R32 DC Inverter Free Cooling Air Cooled Industrial Glycol Water Chiller/Industrial Air Conditioner Air Cooled Chiller & Heat Pump