48VDC/110DC/220VDC Thyristor Rectifier DC Battery Charger with Ni-CD Battery Bank

Modèle NON.
GZDT

Taille
UN

Certificat
CE

Socket Type
Southamerica

Recyclable
Non-Recyclable

Forfait transport
Wooden

spécification
30VDC/48VDC/110VDC/220VDC

Marque déposée
HEMG

Origine
Chine

Capacité de production
5000set/Year

La description

7.10 Technical Particulars & Guarantees of
110V DC Sub-Station Battery

SL. Non. La description Unit BPDB’s Requirement Manufacturers Guaranteed Particulars
1 Manufacturers name & country To be mentioned HEMG/CHINA
2 Manufacturers model no. To be mentioned GNZ100
3 Taper Nickel Cadmium Alkaline (enclosed type) Nickel cadmium Alkaline(open type)
4 Operating Voltage V DC 110 110
5 Continuous Discharge Current at rate of 10 hour & Final Cell Voltage 1.1 Volt Amp 10 10UN
6 Short Time Discharge Current at rate of 2 hour & Final Cell Voltage 1.1 Volt Amp 50 50UN
7 Electrolyte type To be mentioned Alkaline solutions
8 Capacity at 10 hour rate AH 100 100Ah
9 Discharge Voltage Volt 1.3 Per Cell 1.3 Per Cell
10 Charging Voltage (Normal) Volt 1.6 Per Cell 1.6 Per Cell
11 Number of cells Nos. 92 nos. +5nos. Spare 92 nos.+5 nos. Spare
12 Voltage per cell V 1.2 1.2V
13 Charging Voltage (Maximum) Volt 1.75 Per Cell 1.75 Per cell
14 Normal float charge rate UN To be mentioned 0.2UN-0.3UN
15 Maximum boost charge rate UN To be mentioned 30UN
16 Amp hour efficiency at:
a) 10 hour rate
b) 1 hour rate

%
%

To be mentioned
To be mentioned
108%
60%
17 Size of cell Mm To be mentioned 165*105*345millimètre(ABS or PP container)
18 Weight of cell and electrolyte Kg To be mentioned 9.3Kg/1.70Kg
19 Standard As per Latest Edition of applicable IEC-60623 IEC-60623
20 Specific gravity of electrolyte To be mentioned 1.20±0.02g/cm3
21 Release pressure for valve regulated type Kg/m2 To be mentioned 0.005×10-4Kg/m2
22 Volume of electrolyte per cell Ml To be mentioned 1.8L
23 Volume of reserve electrolyte per cell Ml To be mentioned 0.78L
24 No of electrode plates per cell Nos. To be mentioned Positive 12 pièces
Negative 11 pièces
25 Type of racks
a) Hauteur
b) Width
c) Depth


To be mentioned
Steel
3360
640
626
26 Cell dimension:
a) Hauteur
b) Width
c) Depth

To be mentioned

165
105
345
27 Rack Dimensions
a) Hauteur
b) Width
c) Depth

3360
640
626
28 Recycling facilities for unserviceable batteries available or not Y/N To be mentioned Non


Seal & Signature of the Manufacturer Seal & Signature of the Bidder

7.11 Technical Particulars & Guarantees of Sub-Station
110V DC Battery Charger

SL. Non. La description Unit BPDB’s Requirement Manufacturers Guaranteed Particulars
1 Manufacturers name & country To be mentioned HEMG
2 Manufacturers model no. To be mentioned GZDT-110V/50UN
3 Rating To be mentioned 10KVA
4 Rated Input voltage range V AC 415 V ± 10% 415V±10%
5 Fréquence nominale Hz 50 Hz (±3%) 50Hz±3%
6 No of Phase 03 03
7 Contrôle Shall be mentioned PLC+Touch screen
8 Communication module for station automation Shall be provided 485
9 Rectifier type Silicon Silicon
10 Nominal output voltage V DC 110 110V
11 Charging operating control Boost and floating charge, automatic with manual operation manual operation
12 Output current A DC ≥ 40 50UN
13 Continuous current rating 110% of rated current 110% of rated current
14 Efficiency % ≥ 85 ≥85%
15 Voltage regulation % ± 0.5 ±0.5%
16 Ripple voltage mV 150 ≤150
17 Boost charging voltage V/cell 1.6 to 1.75 (programmable) programmble
18 Boost charging time Hour Programmable programmable
19 Operating temperature °C 0 pour 50 0~50
20 Humidité % 95 95%
21 Audible noise dB 65 ≤65
22 Facilities for paralleling with another charger Shall be provided One charger
23 Protection against surge voltage Shall be provided Surge arrester
24 Protection against reverse polarity Isolation diodes
25 Provision for current limiting 110%
26 Provision of constant voltage charge 90V -130V 80-160V
27 Provision of showing earth leakage current by analog meter 20mA
28 Battery Temperature compensation Shall be incorporated. -2~3mv/C(20C)
29 Alarm annunciator independent of the microprocessor Shall be provided PLC
30 Analog meters for voltage and current measurement of input output and battery power
Shall be mentioned
Dc voltmeter
Dc current meter
31 Dimension Shall be mentioned 800×600×2260mm
32 Output voltage range
a) Normal charge
b) Float charge
c) Boost charge

V DC
V DC
V DC

110 V ± 1%
120 V ± 1%
150 V ± 1%

110 V ± 1%
120 V ± 1%
150 V ± 1%
33 Normal/boost charge independent units? Oui/Non To be mentioned Non
34 Output current UN 50 50
35 Rated Battery Current UN 20 20
36 Efficiency % To be mentioned 80%
37 Ripple Voltage % 3% 3%
38 Type of AVR Static 20V
39 Installation Break Down Voltage KV 2KV for 1 Minute 2KV for 1 Minute
40 Type of rectifier Thyristor To be mentioned Thyristor
41 MCCB
a) Quantité Nos. MCB will be provided near AC input & DC Output Meet customer needs
b) Rating UN AC input MCB-50A DC Output MCB-63A AC input MCB-50A DC Output MCB-63A
42 Standard As per Latest Edition of Applicable IEC-60146 IEC-60146