Beschreibung
CNC Changeover Capacitor AC Contactor Cj19c High Quality 110V 220V 380V Electric Contactor (CJ19)
CJ19i contactor for capacitor switching (hereinafter called contactor) is suitable for the circuit of AC 50Hz/60Hz with rated rated voltage up to 690V. It is mainly used to add low voltage reactive power compensation equipment or cut off low voltage parallel capacitor. The contactor is equipped with a device to suppress the inrush current, which can effectively reduce the impact of the making inrush current on the capacitor and suppress the over-voltage when the capacitor is cut off.
Standard: IEC/EN 60947-4-1.
Contactor model | CJ19i-25 CJ19s-25 | CJ19i-32 CJ19s-32 | CJ19i-43 CJ19s-43 | CJ19i-63 CJ19s-63 | CJ19i-80 CJ19s-80 | CJ19i-95 CJ19s-95 | CJ19i-115 CJ19s-115 | ||
Main circuit features | |||||||||
Rated operational voltage(Ue) | v | 380/400 | |||||||
Rated isolation voltage(Ui) | v | 690 | |||||||
Rated current of controllable capacitor(In) | AC-6b 400V | EIN | 17 | 29 | 36 | 43 | 58 | 72 | 87 |
Rated capacity of controllable | AC-6b 230V | kVar | 6 | 9 | 10 | 15 | 22 | 22.5 | 35 |
AC-6b 400V | kVar | 12 | 18 | 20 | 30 | 40 | 45 | 60 | |
capacitor(Qn) | |||||||||
Rated conventional heating current(Ith) | EIN | 25 | 32 | 43 | 63 | 80 | 95 | 115 | |
Restrained surge capacity | EIN | ≤35In | ≤55In | ||||||
Mechanical durability | 104 mal | 100 | |||||||
Electrical durability | AC-6b 400V 104 mal | 15 | 12 | ||||||
Operating frequency cycles/h | AC-6b 400V times/h | 300 | 120 | ||||||
Coil features | |||||||||
Controlled power voltage (Us) | AC50Hz | v | 110, 220, 380 | ||||||
Operation voltage range | operation voltage | v | 85%~110%Us when install inclination angle is +22.5°; 70%~120%Us when install inclination angle is ±5°; | ||||||
release voltage | v | 20%~75%Us when install inclination angle is +22.5°; 20%~65%Us when install inclination angle is ±5°; | |||||||
Auxiliary contact features | |||||||||
Number of auxiliary contact | 12, 21 | ||||||||
Rated conventional heating current(Ith) | EIN | 10 | |||||||
The minimum load can be connected to | 6V×10mA |