وصف
7.10 Technical Particulars & Guarantees of
110V DC Sub-Station Battery
110V DC Sub-Station Battery
إس إل. لا. | وصف | وحدة | BPDB’s Requirement | Manufacturers Guaranteed Particulars |
1 | Manufacturers name & country | – | To be mentioned | HEMG/CHINA |
2 | Manufacturers model no. | – | To be mentioned | GNZ100 |
3 | اكتب | – | Nickel Cadmium Alkaline (enclosed type) | Nickel cadmium Alkaline(open type) |
4 | Operating Voltage | V DC | 110 | 110 |
5 | Continuous Discharge Current at rate of 10 hour & Final Cell Voltage 1.1 Volt | أمبير | 10 | 10أ |
6 | Short Time Discharge Current at rate of 2 hour & Final Cell Voltage 1.1 Volt | أمبير | 50 | 50أ |
7 | Electrolyte type | – | To be mentioned | Alkaline solutions |
8 | Capacity at 10 hour rate | AH | 100 | 100اه |
9 | Discharge Voltage | Volt | 1.3 Per Cell | 1.3 Per Cell |
10 | Charging Voltage (Normal) | Volt | 1.6 Per Cell | 1.6 Per Cell |
11 | Number of cells | Nos. | 92 nos. +5nos. Spare | 92 nos.+5 nos. Spare |
12 | Voltage per cell | الخامس | 1.2 | 1.2الخامس |
13 | Charging Voltage (Maximum) | Volt | 1.75 Per Cell | 1.75 Per cell |
14 | Normal float charge rate | أ | To be mentioned | 0.2أ-0.3أ |
15 | Maximum boost charge rate | أ | To be mentioned | 30أ |
16 | Amp hour efficiency at: أ) 10 hour rate b) 1 hour rate |
% % |
To be mentioned To be mentioned |
108% 60% |
17 | Size of cell | Mm | To be mentioned | 165*105*345مم(ABS or PP container) |
18 | Weight of cell and electrolyte | كجم | To be mentioned | 9.3كجم/1.70كجم |
19 | Standard | – | As per Latest Edition of applicable IEC-60623 | IEC-60623 |
20 | Specific gravity of electrolyte | To be mentioned | 1.20±0.02ز/cm3 | |
21 | Release pressure for valve regulated type | كجم/m2 | To be mentioned | 0.005×10-4Kg/m2 |
22 | Volume of electrolyte per cell | Ml | To be mentioned | 1.8ل |
23 | Volume of reserve electrolyte per cell | Ml | To be mentioned | 0.78ل |
24 | No of electrode plates per cell | Nos. | To be mentioned | Positive 12 جهاز كمبيوتر شخصى Negative 11 جهاز كمبيوتر شخصى |
25 | Type of racks أ) ارتفاع b) Width ج) Depth |
To be mentioned |
Steel 3360 640 626 |
|
26 | Cell dimension: أ) ارتفاع b) Width ج) Depth |
To be mentioned |
165 105 345 |
|
27 | Rack Dimensions أ) ارتفاع b) Width ج) Depth |
3360 640 626 |
||
28 | Recycling facilities for unserviceable batteries available or not | ي/N | To be mentioned | لا |
Seal & Signature of the Manufacturer Seal & Signature of the Bidder
7.11 Technical Particulars & Guarantees of Sub-Station
110V DC Battery Charger
إس إل. لا. | وصف | وحدة | BPDB’s Requirement | Manufacturers Guaranteed Particulars |
1 | Manufacturers name & country | – | To be mentioned | HEMG |
2 | Manufacturers model no. | – | To be mentioned | GZDT-110V/50أ |
3 | Rating | – | To be mentioned | 10KVA |
4 | Rated Input voltage range | فولت تيار متردد | 415 الخامس ± 10% | 415الخامس±10% |
5 | Rated Frequency | هرتز | 50 هرتز (±3%) | 50هرتز±3% |
6 | No of Phase | – | 03 | 03 |
7 | Control | Shall be mentioned | PLC+Touch screen | |
8 | Communication module for station automation | Shall be provided | 485 | |
9 | Rectifier type | Silicon | Silicon | |
10 | Nominal output voltage | V DC | 110 | 110الخامس |
11 | Charging operating control | Boost and floating charge, automatic with manual operation | manual operation | |
12 | Output current | A DC | ≥ 40 | 50أ |
13 | Continuous current rating | 110% of rated current | 110% of rated current | |
14 | كفاءة | % | ≥ 85 | ≥85% |
15 | Voltage regulation | % | ± 0.5 | ≥±0.5% |
16 | Ripple voltage | mV | ≥ 150 | ≤150 |
17 | Boost charging voltage | الخامس/cell | 1.6 to 1.75 (programmable) | programmble |
18 | Boost charging time | Hour | Programmable | programmable |
19 | درجة حرارة التشغيل | °C | 0 ل 50 | 0~50 |
20 | رطوبة | % | 95 | 95% |
21 | Audible noise | ديسيبل | ≥ 65 | ≤65 |
22 | Facilities for paralleling with another charger | Shall be provided | One charger | |
23 | Protection against surge voltage | Shall be provided | Surge arrester | |
24 | Protection against reverse polarity | Isolation diodes | ||
25 | Provision for current limiting | 110% | ||
26 | Provision of constant voltage charge 90V -130V | 80-160الخامس | ||
27 | Provision of showing earth leakage current by analog meter | 20أماه | ||
28 | Battery Temperature compensation | Shall be incorporated. | -2~3mv/درجة مئوية(20درجة مئوية) | |
29 | Alarm annunciator independent of the microprocessor | Shall be provided | PLC | |
30 | Analog meters for voltage and current measurement of input output and battery power | Shall be mentioned |
Dc voltmeter Dc current meter |
|
31 | البعد | Shall be mentioned | 800×600×2260mm | |
32 | Output voltage range أ) Normal charge b) Float charge ج) Boost charge |
V DC V DC V DC |
110 الخامس ± 1% 120 الخامس ± 1% 150 الخامس ± 1% |
110 الخامس ± 1% 120 الخامس ± 1% 150 الخامس ± 1% |
33 | Normal/boost charge independent units? | نعم/لا | To be mentioned | لا |
34 | Output current | أ | 50 | 50 |
35 | Rated Battery Current | أ | 20 | 20 |
36 | كفاءة | % | To be mentioned | 80% |
37 | Ripple Voltage | % | 3% | 3% |
38 | Type of AVR | – | Static | 20الخامس |
39 | Installation Break Down Voltage | KV | 2KV for 1 Minute | 2KV for 1 Minute |
40 | Type of rectifier | Thyristor | To be mentioned | Thyristor |
41 | MCCB | |||
أ) Quantity | Nos. | MCB will be provided near AC input & DC Output | Meet customer needs | |
b) Rating | أ | AC input MCB-50A DC Output MCB-63A | AC input MCB-50A DC Output MCB-63A | |
42 | Standard | – | As per Latest Edition of Applicable IEC-60146 | IEC-60146 |