وصف
Jichai Brand Generator is designed and manufactured to be high quality, long usage life, easy operation, low maintenance cost, high intelligence with low engine speed, low fuel consumption, low gas quality requirement, tough environmental adaptability, high stability and low fluctuation. The generator is desirable for industrial power solution.
MAIN SPECIFICATIONS OF GAS GENERATOR SET
نموذج | 1200GF-T | Gas Engine Model | H16V190ZLT-2 | |
Rated power | 1200kW/1500KVA | المولد | Siemens Series | |
الفولطية | 400 الخامس | Starting method | 24V DC electric start | |
Rated speed | 1000دورة في الدقيقة | Voltage regulation | Automatic | |
Rated frequency | 50هرتز | Cooling Mode | Close type water cool | |
التصنيف الحالي | 2164أ | Heat Consumption | 10200kJ/kWh | |
Power factor | 0.8 Lagging | البعد (مم) | 6583x2180x2540mm | |
Control mode | Electric control | الوزن الصافي (كلغ) | 24000 |
MAIN ELECTRICAL PERFORMANCE OF THE GAS GENERATOR
الجهد االكهربى | |||
Stabilized regulation | Instantaneous regulation | Recovery time | Fluctuation |
±2.5% | +20% – 15% | 1.5س | 0.5% |
تكرار | |||
Stabilized regulation | Instantaneous regulation | Recovery time | Fluctuation |
0-5% adjustable | +10%,-10% | < 7 س | 0.5% |
MAIN SPECIFICATIONS OF GAS ENGINE
نموذج | H16V190ZLT-2 |
Rated power | 1320كيلوواط (1650KVA) |
Number and layout of cylinders: | 16-cylinders, V-type, 60° included angle |
اكتب | Four strokes, Closed type water cooled, Turbo-charged, Electronic ignition, Electronic speed governor |
Ignition type | Spark plug ignition |
Intake gas pressure required | 100-400 kPa before gas pressure regulator |
Bore´Stroke | 190´215 mm |
Speed Governor | (Woodward) EGS-02 Electric governor |
Oil consumption | £ 0.8g/kWh |
Total lubricating oil capacity (Liters) | 460ل |
Exhaust temperature (before turbine) | £ 680 °C |
Heavy overhauling period | 36,000ح |
MAIN SPECIFICATIONS OF ALTERNATOR
Alternator model | Exciting model | Insulation class | اتصال | Cooling | Structure type |
1FC6564-6LA42 (SIEMENS) | فرش | Class F | 3-phase, 4-wire | Air cooled | AVR and reactive droop regulator assembled in alternator |
(Kindly Noted: data shown in above table tested under standard working condition: 25 Dec C, atmospheric pressure 100kPa, relative humidity 30%, altitude <1000m.)
CONTROL PANEL
Control panel is panel type, vertical structure, model is GPL1200. Control panel is equipped with meters showing various parameters of operating status, automatic air switch and timer. All of the electric cells possess three-proof functions.
The Generator possesses the following automatic monitoring and protective functions:
أ) Audio or visual alarm for:
– High oil and water temperature
– Low oil pressure
– Over current
– Short circuit
– Over-speed
– Reverse power
ب) Shut-off for:
– Low oil pressure
– Over-speed
– Short circuit
– Over-speed
– Reverse power
ج) Trip-off for:
– Over-current
– Short circuit
– Reverse power
The generator can not only supply power directly to load but also can be paralleled running.
Any moe questions,feel free to contact us: +86=182= 5419=0201 [البريد الإلكتروني محمي] outlook. com
OPTIONAL DEVICE
Steel Soundproof Container (sound attenuated canopy)
CHP/ Cogeneration/CCHP Trigeneration
ATS and Synchronization Parallelling Panel
Oil and Water Heater