Hot Sale Motor Protection Circuit Breaker Elv_M Series

Model NO.
ELV_-M Series

Rated Insulation Voltage Ui
690V

Rated Operational Voltage Ue
230/240,400/415

Rated Impulse Withstand Voltage Uimp
8

Electrical Life in AC-3 (Times)
10000

Mechanical Life (Times)
20000

Max.Operating Altitude (Meters)
Less Than 2000

Transport Package
Carton

Specification
small

Trademark
ELECO

Origin
Zhejiang, China

Production Capacity
10000PCS/Month

Description

Application

ELV_-M series motor protection circuit breakers is mainly used for the overload and short circuit protaction of the motor in AC 50/60Hz, up to 660V, 0.1-80A power circuit, as a full voltage starter and cut off the motor, under the AC3 load or for the overload and short circuit protaction of the circuit and power equipment in the power distribution network.
 

Specifications
Type 230/240V 400/415V 440V 500V 690V
ELV2-M aM gl aM gl aM gl aM gl aM gl
  A A A A A A A A A A A
01-06 0.1-1.6
07 2.5 16 20
08 4 25 32
10 6.3 50 63 50 63 32 40
14 10 50 63 50 63 32 40
16 14 63 80 50 63 50 63 40 50
20 18 63 80 50 63 50 63 40 50
21 23 80 100 80 100 63 80 50 63 40 50
22 25 80 100 80 100 63 80 50 63 40 50
32 32 80 100 80 100 63 80 50 63 40 50
Operation performance for motor protection circuit breaker
Serial no. Rated current Inm(A) Operating cycle frequency(time/h) Operating cycle electric life(times) Mechanical life(times) Overall(times)
1 ELV2-M 120 2000 10000 12000
2 ELV3-M 120 2000 10000 12000
Overload balance characteristics
Step no. Testing current(A) Start situation Limited time Pre-engage result Ambient air temperature
1 1.05 Cold state t≥2h non-trip 20ºC±2ºC
2 1.2 Hot state (The current rise steadily to a xed value after step1) t<2h trip 20ºC±2ºC
3 1.5 It starts after the heat balance of 1.0In current. Trip 10A t<2min
Grade10 t<4min

 
Trip
trip
20ºC±2ºC
4 7.2 Cold state Trip 10A 2s<t≤10s
Grade 10 4s≤t≤10s
Trip
 
trip
20ºC±2ºC
Overload non-balance characteristics
Step no. Testing current(A) Start situation Limited time Pre-engage result Ambient air temperature
Two phase Third-phase
1 1.0 0.9 Cold state T≥2h non-trip 20ºC±2ºC
2 1.15 0 Hot state(The current rise steadily to a xed value after step 1) T<2h trip 20ºC±2ºC

Hot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M SeriesHot Sale Motor Protection Circuit Breaker Elv_M Series